MK Engineering Works is a leading manufacturer and supplier of Low Voltage (LV) and Medium Voltage (MV) electrical panels. With a commitment to excellence and a track record of delivering top-quality electrical solutions, MK Engineering plays a pivotal role in powering various industries and infrastructure projects.

See Our Achievements

LV Panels Products

  1. Generator Synchronization panel
  2. ATS/AMF panel
  3. Main LT panel
  4. Distribution Board (Concealed/Wall Mounted/Floor standing)
  5. Automatic and Manual Power factor control and improvement panel
  6. Monitoring and Metering panel
  7. MCC panel

MV Panels Products

  1. 11kV VCB Incoming Panel
  2. 11kV VCB Outgoing Panel
  3. 11kV VCB BUS Coupler panel
  4. 11kV VCB WAPDA Industrial Metering / Protection Panel (As per WAPDA specs)

Components of Metal-Clad Switchgear Panels

Sr. NoItem DescriptionIncoming PanelOutgoing PanelBus-Coupler PanelCapacitor Control panelConsumer PanelIndustrial PanelRing main Panel
1Circuit Breaker1111111
2Load Break Switch--2---2
3Earthing Switch-1(i)-1(i)1(i)--
4Single Phase, 2-core CT for over-current protection and metering33-3--3
5Single Phase, 1-core CT for over current protection----333
6Single Phase, 1-core CT for metering----333
7Single Phase, 1-core CT for Differential Protection3------
8Single phase voltage transformer3---333
9Surge Arrestors-3-33--
10Over-current and earth fault relay1(ii)1(ii)-1(iii)1(ii)1(iv)1(iv)
11Two step capacitor unbalance detection relay---1(iii)---
12Under voltage/over voltage relay---1---
13DC trip circuit supervision relay (TCS)22-221(v)1(v)
14Trip & Lockout relay---1---
15Energy Meter11--111
16Ammeter33-1133
17Voltmeter 0-15kV with 7 position selector switches1---111
18Power factor meter11-1111
19Hooter and its acknowledgment1--1---
20Power Quality analyzer1(i)---1(i)--

i. If required by Purchaser/end user

ii. Three phase four element over current & earth fault relay shall be used as per clause 12.5

Breaker Characteristics and Rating

1Nominal Voltage11kV
2Rated Voltage12KV
3
Normal Current at reference ambient temp. 50 C
i) Incoming & Bus-coupler panels
ii)Other switchgear panel
-
2500A
630A
4Rated frequency50Hz
5Rated auxiliary circuit DC voltage110V
6Rated short circuit breaker current25KA
7Rated Peak withstand current63KA
8Rated short circuit making current63KA
9Duration of short circuit1 sec
10First pole to clear factor1.5
11Rated TRV (Peak) for terminal fault20.6KV
12Rated TRV (Peak) for out of phase30.6KV
13One-minute AC withstand voltage36KV
14Lightning Impulse withstand voltage95KV
15Single capacitor bank breaking currentAs per IEC
16Rate of rise of recovery voltage (RRRV)As per IEC
17
Operating sequence
i) Outgoing consumer and capacitor bank Control panel (with fast auto-reclosing)
ii) Other (without fast auto-reclosing)
-
O-3min-CO-3min-CO
O-3min-CO-3min-CO
18Beaker timeAs per IEC
19Dead timeAs per IEC
20Opening timeAs per IEC
21Closing timeAs per IEC
22Spring charging time≤15sec
23Close-Open timeAs per IEC
24
Circuit breaker class
i) w.r.t Mechanical Endurance
ii) w.r.t Electrical Endurance
iii) w.r.t Capacitive Current Breaking
iv) w.r.t Connection to Cable
-
M2
E2
C2
S1